XI581/2 BUSWIDE OPERATOR INTERFACE
34 EN2B-0126 (74-3554-8)
Start-up and Configuration
Purpose To start up the controller and configure its hardware interfaces.
Reset Controller 1. Reset the controller by pressing the square reset switch on the CPU module.
RESULT: The screen displays system information and version number.
CONTINUE is highlighted by default.
HONEYWELL
EXCEL—5000
produced in
SCHOENAICH GERMANY
SYSTEM VERSION : V2.03.00
CONTINUE
2. Press Enter (↵) to select CONTINUE.
RESULT: The 'date and time' screen is displayed. Also displayed is whether or
not modem communication is enabled and the size of application
memory. Several start-up options are listed. Controller Setup is
highlighted by default.
01.01.1999 Controller: 23
14:45 Modem Part: inactive
Applic. Mem. Size: 128 KB
Controller Setup
Application Selection
Data Point Wiring Check
Modem Part Shows whether modem communication is enabled for the
controller. Disabling modem communication frees up
additional memory resources. Enabling/disabling modem
communication is done in a later screen.
Applic.
Mem. Size Shows the amount of memory reserved for the application.
Reducing this number frees additional memory resources. The
application memory size is changed in a later screen.
Controller
Setup Displays screens for configuring the hardware interfaces for
the controller.
Application
Selection Loads a user-selected application program from Flash
EPROM to RAM, or permits an application download.
Data Point
Wiring Check Starts a test mode with default data points to allow easy
checkout of input/output wiring.
Change Date/Time/Controller Number 3. To modify the date, time, or controller number, use the arrow keys to move to
and highlight appropriate field. Press Enter (↵) to complete the selection.
RESULT: The first, left-most digit that you can modify blinks.
4. Use the plus or minus keys to increment or decrement the digit, respectively.
When the digit is correct, use the arrow keys to move to the next digit. Repeat
this procedure until all digits are correct. Press Enter (↵) to complete the
modification. Repeat for any other fields to be modified.