ALPHABETIC REFERENCE XI581/2 BUSWIDE OPERATOR INTERFACE
EN2B-0126 (74-3554-8) 58
Purpose To turn off point trending for one or more user addresses.
Access Level You must have access level 3 to perform this task.
Select Point from Main Menu 1. At the Main Menu, use the arrow keys to move to and highlight Data Points.
Press Enter () to complete the selection.
RESULT: The 'Data Points' screen appears. User Address is highlighted by
default.
Data Points
User Address Suppress Alarm
Manual Operation Add Template
Accumul. Runtime Delete Template
Type Selection Modify Template
Points in Trend Template Search
Select Trend Option 2. Use the arrow keys to move to and highlight Points in Trend. Press Enter () to
complete the selection.
RESULT: The display window lists points with trending capability.
Points in Trend
Exhaust_fan
Hall_main_lights
Main_water_meter 1
Conf_room_temp
NOTE: All trend points may not be able to appear in the display window at
the same time.
Select a Point 3. Use the arrow keys to move to and highlight the point you want to disable from
trending. Press Enter () to complete the selection.
NOTE: Additional user-defined text may appear on the line beneath the user
address.
RESULT: The window allows you to disable the point from reporting trend
information.
Points in Trend
Cafeteria_room_temp.
Trend Logging: ON
Back
Disable Point from Trending 4. Use the arrow keys to move to and highlight the Point in Trend field. Then
press Enter () to complete the selection.
RESULT: The entry in the Point in Trend field starts blinking.
5. Press the plus or minus keys to change the Point in trend to OFF. Then press
Enter () to complete the selection.
RESULT: The entry in the Point in Trend field stops blinking but is still high-
lighted.
6. Use the arrow keys to move to and highlight Back. Then press Enter ().
RESULT: The 'Data Points' screen redisplays.
Suppressing Alarm Reporting for a Point