ALPHABETIC REFERENCE XI581/2 BUSWIDE OPERATOR INTERFACE
EN2B-0126 (74-3554-8) 78
RESULT: The top line of the window displays the selected time
program. The remaining lines display the types of Time
Programs ('Today', 'Daily Programme', etc.).
c. Use the arrow keys to move to and highlight Daily Programme and then
press Enter (↵) to complete the selection.
RESULT: The top line of the display window shows the selected time
program. The remaining lines list daily program functions
('Modify', 'New', 'Delete', and 'Copy').
Time Programme: Time Program 1
Modify Delete
New Copy
New Daily Program Function 2. Use the arrow keys to move to and highlight the New daily program function.
Press Enter (↵) to complete the selection.
RESULT: The controller creates a new daily program and assigns it a non-
descriptive name: the letters TZ (for Time Program) followed by a
number. The display window also lists the various points that can be
controlled by the new daily program.
Time Progr. : Time Program 1
Daily Progr.: TZ 4
Conf._room_temp. ▲
▲▲
▲
Cafeteria_temp. 1
Office_room_temp. ■
Main_lights ▼
NOTE: All points may not be able to appear in the display window at the
same time.
Select a Point 3. Use the arrow keys to move to and highlight the point to which the first switch
point applies. Then press Enter (↵) to complete the selection.
RESULT: The user address associated with the selected point appears in the
'Address' field of the 'Switch Point' screen.
Time Progr.: Time Program 1
Daily Progr.: TZ 4
Address: Conf._room_temp.
Time : 00:00
Value : 0 F Opt.: OFF
Next Previous New Delete Back
Switch Point Information 4. Enter new switch point information as follows:
Time Time of day when the change in state or value should occur.
Time is in 24-hour (HH.MM) notation where HH=00-23 and
MM=00-59. For example, enter the time you want the tem-
perature in the conference room to change.
Value If the selected point is an analog point, enter the new value
that the controller should execute (for example, the new set
point temperature for the conference room). If the selected
point is a digital point, enter the new state (for example, OFF,
ON, or AUTO).
Opt. If the DDC program uses this point for optimization, select ON
to enable optimization or OFF to disable optimization. If the