49 3:1:0 FC degraded missing_B_port,loop_failure
…
107 4:9:0 FC failed prolonged_not_ready,missing_A_port,relocating
cli% showcage -d cage3
Id Name LoopA Pos.A LoopB Pos.B Drives Temp RevA RevB Model Side
1 cage3 --- 1 0:0:1 1 8 20-23 402e - DCS2 SFF
-----------Cage detail info for cage3 ---------
Position: ---
Interface Board Info Card0 Card1
Firmware_status Current -
Product_Rev 402e -
State(self,partner) OK,OK -,-
VendorID,ProductID HP,DCS2 -,-
Master_CPU Yes -
SAS_Addr 50050CC1178EA0BE -
Link_Speed(DP1,DP2) 6.0Gbps,Unknown -,-
PS PSState ACState DCState Fan State Fan0_Speed Fan1_Speed
ps0 OK OK OK OK Low Low
ps1 OK OK OK OK Low Low
-------------Drive Info------------------ ----PortA---- ----PortB----
Drive DeviceName State Temp(C) LoopState LoopState
0:0 5000c500720387e0 Normal 20 - OK
0:1 5000c50072039188 Normal 21 - OK
0:2 5000c500720387b0 Normal 21 - OK
0:3 5000c500720395b4 Normal 21 - OK
0:4 5000c50072036fbc Normal 21 - OK
0:5 5000c50072039fc0 Normal 21 - OK
0:6 5000c50072037250 Normal 21 - OK
0:7 5000c5005737cc0c Normal 23 - OK
pd Example 2
cli% checkhealth -detail pd
Checking pd
Component -------------------Summary Description------------------- Qty
PD Unbalanced PD types in cages 1
PD PDs that a degraded 1
------------------------------------------------------------------------
2 total 2
Component --Identifier-- ----------------------------Detailed Description----------------------------
PD Cage:0 PDs FC/10K/450GB unbalanced. Primary path: 5 on Node:0,3 on Node:1
PD disk:0 Degraded States: missing_A_port,servicing
--------------------------------------------------------------------------------------------
2 total
pd Suggested Action 2
The primary and secondary I/O paths for drives (PDs) are balanced between nodes. The primary
path is indicated in the showpd -path output and by an asterisk in the showpd output. An
imbalance of active ports is usually caused by a non-functioning path/loop to a cage, or because
an odd number of drives is installed or detected, or drives were installed in the wrong slots. To
diagnose further, use CLI commands such as showpd, showpd -path, showcage, and showcage
-d.
cli% showcage -d cage0
Id Name LoopA Pos.A LoopB Pos.B Drives Temp RevA RevB Model FormFactor
0 cage0 1:0:1 0 0:0:1 0 8 20-22 402e 402e DCN1 SFF
-----------Cage detail info for cage3 ---------
Troubleshooting Storage System Components 55