400 Series
EN - 30
6. If the RCD does not trip, the
instrument gives a double
acoustic signal which signals
the positive result of the test
and then displays a screen
similar to the one reported
here to the side
RCD
> 999ms
FRQ=50.0Hz Ut=1.4V
VP-N=228V VP-Pe=228V
0° or 180° type current
Tripping time of the RCD
Detected value for contact voltage Ut
compared to the nominal value of
the set residual current
RCD OK
x1/2 30mA 50V
Func IdN RCD UL
7.
The results displayed can be saved by pressing the SAVE key twice or the
SAVE key and, subsequently, the ENTER key (§ 8.1)
6.4.3. x1, x2, x5 mode
As an alternative:
5.
Press the GO/STOP key on the instrument or the START key on
the remote probe once. The instrument will start measuring with
a “0°” type current, injecting a current in phase with the positive
half-wave of voltage.
Or:
5.
Press the GO/STOP key on the instrument twice or the START key
on the remote probe before the hyphens disappear. The instrument
will start measuring with a “180°” type current, injecting a current in
phase with the negative half-wave of voltage.
CAUTION
If message “Measuring…” appears on the display, the instrument is
performing measurement. During this whole stage, do not disconnect the
test leads of the instrument from the mains.
6. The “x5” test is not available for 500mA, 650mA and 1A A-type RCDs
7. When the RCD trips and
separates the circuit, if the
tripping time is within the
limits reported in Table 5, the
instrument gives a double
acoustic signal which signals
the positive result of the test
and then displays a screen
similar to the one reported
here to the side
RCD
29ms
FRQ=50.0Hz Ut=1.4V
VP-N=228V VP-Pe=228V
0° or 180° type current
Tripping time of the RCD
Detected value for contact voltage Ut
compared to the nominal value of
the set residual current
RCD OK
x1 30mA 50V
Func IdN RCD UL
8.
The results displayed can be saved by pressing the SAVE key twice or the
SAVE key and, subsequently, the ENTER key (§ 8.1)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HT 400 Series and is the answer not in the manual?

HT 400 Series Specifications

General IconGeneral
TypeDigital Multimeter
Diode TestYes
Auto RangingYes
Data HoldYes
Operating Temperature0°C to 40°C
DC Current Range400μA to 10A
AC Current Range400μA to 10A
Resistance Range400Ω to 40MΩ
Continuity TestYes
DisplayLCD, 4000 counts
Measurement RangeAs per individual functions

Related product manuals