Formula used for calculating the prospective short circuit current:
PN
N
CC
Z
U
I
where: Z
PN
is the measured phase-to-neutral impedance
U
N
is the nominal phase-to-neutral voltage
U
N
= 127V if V
P-N meas
150V
U
N
= 230V or U
N
= 240V (§ 5.2.3) if V
P-N meas
> 150V
8.
9.
The results displayed can be saved by pressing the SAVE key twice or the
SAVE key and, subsequently, the ENTER key (§ 8.1)
6.5.2. P-P mode
6.
Press the GO/STOP key on the instrument or the START key on remote
probe. The instrument will start the measurement.
CAUTION
If message “Measuring…” appears on the display, the instrument is
performing measurement. During this whole stage, do not disconnect the
test leads of the instrument from the mains.
7. Once test is completed, if the
measured impedance value
is lower than the full scale,
the instrument gives a
double acoustic signal and
then displays a screen
similar to the one reported
here to the side
LOOP
0.57
701A
FRQ=50.0Hz
VP-P=402V VP-Pe=230V
Measured impedance value
Prospective short circuit current
P-P and P-PE measured voltages
P-P STD
Func Mod.
Formula used for calculating the prospective short circuit current:
PP
N
CC
Z
U
I
where: Z
PP
is the measured phase-to-phase impedance
U
N
is the nominal phase-to-phase voltage
U
N
= 127V if V
P-P meas
150V
U
N
= 230V or U
N
= 240V (§ 5.2.3) if 150V < V
P-P meas
265V
U
N
= 400V or U
N
= 415V (§ 5.2.3) if V
P-P meas
> 265V
8.
9.
The results displayed can be saved by pressing the SAVE key twice or the
SAVE key and, subsequently, the ENTER key (§ 8.1)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HT 400 Series and is the answer not in the manual?

HT 400 Series Specifications

General IconGeneral
TypeDigital Multimeter
Diode TestYes
Auto RangingYes
Data HoldYes
Operating Temperature0°C to 40°C
DC Current Range400μA to 10A
AC Current Range400μA to 10A
Resistance Range400Ω to 40MΩ
Continuity TestYes
DisplayLCD, 4000 counts
Measurement RangeAs per individual functions

Related product manuals