EasyManua.ls Logo

HT 400 Series - 6.5. LOOP: Measurement of Line;Loop Impedance

HT 400 Series
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
400 Series
EN - 36
6.5. LOOP: MEASUREMENT OF LINE/LOOP IMPEDANCE
This function is performed according to standard IEC/EN61557-3 and allows measuring
the line impedance, the earth fault loop impedance and the prospective short circuit
current. The following operating modes are available:
P-N the instrument measures impedance between the phase conductor and the
neutral conductor and calculates the prospective phase-to-neutral short circuit
current
P-P the instrument measures impedance between two phase conductors and
calculates the prospective phase-to-phase short circuit current
P-PE the instrument measures the fault loop impedance and calculates the
prospective fault current
CAUTION
The measurement of line impedance or fault loop impedance involves the
circulation of a maximum current according to the technical specifications of
the instrument (§ 11.1). This could cause the tripping of possible
magnetothermal or differential protections at lower tripping currents.
Fig. 15: Instrument connection for 230V single-phase or double-phase P-N line impedance
and P-PE fault loop impedance measurement through shuko cable
Fig. 16: Instrument connection for 230V single-phase or double-phase P-N line impedance
and P-PE fault loop impedance measurement through single cables and remote probe
Fig. 17: Instrument connection for 400V + N + PE three-phase P-N line impedance and
P-PE fault loop impedance measurement through single cables and remote probe

Table of Contents

Related product manuals