13. If the instrument detects an
extremely high earth
resistance, so that it deems
the earth conductor or the
earthing absent, it does not
perform the test and displays
the message reported here
to the side. Check the
efficiency of the protective
conductor and the earthing
RCD
---ms
FRQ=50.0Hz Ut=1.4V
VP-N=231V VP-Pe=160V
MISSING-PE
Inefficient earthing
x1 30mA 50V
Func IdN RCD UL
14. If the instrument detects that, in
case the test should be
performed, a contact voltage
higher than the set limit would
build up in the system being
tested, it does not perform the
test and displays the message
reported here to the side.
Check the efficiency of the
protective conductor and the
earthing
RCD
---ms
FRQ=50.0Hz Ut=0.0V
VP-N=231V VP-Pe=231V
Ut > Ulim
The instrument detects a dangerous
contact voltage
x1 30mA 50V
Func IdN RCD UL
15. If the RCD trips while
performing the preliminary
checks (automatically
performed by the instrument
before performing the
selected test), the instrument
displays the message
reported here to the side.
Check that all loads
connected downstream of the
RCD
---ms
FRQ=50.0Hz Ut=0.0V
VP-N=231V VP-Pe=231V
RCD TRIPPED
RCD tripped during preliminary
checks
x1 30mA 50V
Func IdN RCD UL
RCD being tested are disconnected and that the set value for IdN matches the RCD
being tested
16. If, after repeated tests, the
instrument has overheated,
the message reported here
to the side is displayed. Wait
for this message to
disappear before performing
other tests
RCD
---ms
FRQ=50.0Hz Ut=1.4V
VP-N=231V VP-Pe=231V
Hot temperature
Overheated instrument
x1 30mA 50V
Func IdN RCD UL
17.
The previous anomalous results cannot be saved

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HT 400 Series and is the answer not in the manual?

HT 400 Series Specifications

General IconGeneral
TypeDigital Multimeter
Diode TestYes
Auto RangingYes
Data HoldYes
Operating Temperature0°C to 40°C
DC Current Range400μA to 10A
AC Current Range400μA to 10A
Resistance Range400Ω to 40MΩ
Continuity TestYes
DisplayLCD, 4000 counts
Measurement RangeAs per individual functions

Related product manuals