FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Check whether battery screws are tightened.
Perform a shallow discharge test
(recommended).
Check the exterior of the new main way
component.
Check the operating temperature and
humidity of the new main way.
NetCol5000-C 30 kW
chilled water in-row
precision air conditioner
Water injection is smooth.
The electric heater generates heat.
The chilled water valve handle automatically
rotates to the maximum opening.
Intelligent
battery
monitoring
system
Check the battery management parameter
setting.
Check the CIM connection.
Fire
extinguishin
g system
Check the indicator on the smoke detector.
Check that the alarm beacon works properly.
Table 2-3 Semi-annual maintenance
Clean the skylight steel glass. Clean the glass
using a piece of soft cotton cloth.
NetCol5000-C 30 kW
chilled water in-row
precision air conditioner
Check that no foreign matter exists in the
fan.
Verify that the fan blades are intact.
Check that no abnormal noise is generated
when the fan is running.