FusionModule800 Smart Small Data Center
Maintenance Guide
A Preventive Maintenance Table
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
113
A Preventive Maintenance Table
Monthly preventive maintenance table
Table A-1 Monthly preventive maintenance table
Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
Power Distribution
System
Power indicators
Check the
indicators.
All indicators are
normal.
The power supply
is normal. Replace
the indicator that
generates no or
dim light.
Surge protection
module
Check the surge
protection module
indicator and
miniature circuit
breaker (MCB)
status.
The surge
protection
module
indicator is
steady green.
The MCB is
ON.
If the surge
protection
module
indicator is
steady red,
replace the
surge
protection
module.
If the MCB is
OFF, switch it
on.
Emergency fan
Check whether the
top of the
emergency fan is
blocked.
The top of the fan
is clean and not
blocked.
Clean dust and
foreign matters
from the top of the
fan.

Table of Contents

Other manuals for Huawei FusionModule800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule800 and is the answer not in the manual?

Huawei FusionModule800 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule800
CategoryStorage
LanguageEnglish

Related product manuals