Maintenance Guide
5 Parts Replacement
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
66
Figure 5-30 Removing a humidifier pump
Step 7 Install the new humidifier pump by performing the preceding steps in reverse order, connect
the hoses, and install hose clamps.
Step 8 Clear up the humidifier pump total runtime.
Method 1: Log in to the ECC800 mobile phone or pad app as admin.
a. Choose Home.
b. Tap the cabinet that houses the air conditioner in the micro-module view.
c. Tap the air conditioner to be set in the cabinet layout diagram.
d. Choose Real-time Data > Perf Maint, clear up the humidifier pump total running
time.
Method 2: Log in to the ECC800 WebUI as admin. Choose Monitoring > Air
Conditioner > NetCol5000-A0104 > Controls > Performance Maint Ctrl, clear up the
humidifier pump total running time.
----End
5.3.1.5 Replacing a Wet Film Humidifier
Prerequisites
Tool: Phillips screwdriver.