FusionModule800 Smart Small Data Center
Maintenance Guide
A Preventive Maintenance Table
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
139
Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
Capacity Test
(recommended)
N/A
When the UPS is
backed up,
discharge a battery
to the undervoltage
alarm threshold, to
refresh the capacity
of the battery.
1. Locate the
cause when an
exception is
identified.
2. If the fault
persists,
contact
Huawei
technical
support.
Battery connection
reliability
N/A
1. When battery
strings are
powered off,
check the
reliability of
each connection
point from
positive
terminals to
negative
terminals. All
points are
connected
reliably.
2. Use a torque
wrench to
check the
tightening
torque for each
battery screw.
The torque
meets the
requirements of
the battery
manufacturer.
After checking
that the battery
screws meet the
requirements,
mark the screws
for later check.
1. Rectify any
abnormal
connection.
2. If the fault
persists,
contact
Huawei
technical
support.
ECC800
AC input
N/A
Input voltage:
200240 V AC
Frequency: 4555
Hz
If the input
voltage is
abnormal, check
the power grid and
input cable
connection.

Table of Contents

Other manuals for Huawei FusionModule800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule800 and is the answer not in the manual?

Huawei FusionModule800 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule800
CategoryStorage
LanguageEnglish

Related product manuals