EasyManua.ls Logo

Huawei OptiX OSN 3500 - PDU with the Front Panel; PDU Without the Front Panel; PDU with Short-Circuiting Copper Bars

Huawei OptiX OSN 3500
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
Installing and Routing Power Cables DC Power Distribution Box (DPD63-8-8 PDU)
Power switch area
(A)
Power switch area
(B)
PDU without the front panel
PDU with the front panel
Remove the front panel from the PDU before you install power cables and restore the front panel after you finish the
installation.
Do not install short-circuiting copper bars in the power output areas.
Determine whether short-circuiting copper bars need to be installed in the power input areas based on the site
survey result.
NOTE
DANGER
PDU with short-circuiting copper bars
2-in-1 short-circuiting copper bar (left)
NEG (-)
2-in-1 short-circuiting copper bar (right)
NEG (-)
2-in-1 horizontal short-circuiting copper plates
RTN (+)
A1
(+)
A2
(+)
A3
(+)
A4
(+)
B1
(+)
B2
(+)
B3
(+)
B4
(+)
A1
(-)
A2
(-)
A3
(-)
A4
(-)
B1
(-)
B2
(-)
B3
(-)
B4
(-)
Power input area (B)
Power output area (B) Power output area (A)
Power input area (A)
Power Distribution Guide for the Equipment
Whether to Install Short-
Circuiting Copper Bars
Power Input Power Output
Yes 2 x 63 A, 2 x 125 A 4 x 32 A, 4 x 63 A
No 4 x 32 A, 4 x 63 A 4 x 32 A, 4 x 63 A