EasyManua.ls Logo

Huawei OptiX OSN 3500 - Common Engineering Labels

Huawei OptiX OSN 3500
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
71
2
Common Engineering Labels
Name Content Example Remarks
Labels for
power cables
MN(BC) 48V1
MN(BC) 48V2
MN(BC) BGND
MN(BC) PGND
MN (BC): BC is written right
under MN.
On the loaded cabinet side:
MN identifies the row and
column number of the
power distribution
equipment such as the
control cabinet and cable
distribution box. BC
identifies the row and
column number of the 48 V
wiring terminal. BGND and
PGND are not assigned
rows or columns for
identification.
On the power distribution
cabinet side: Only MN is
required to identify the
cabinet number.
Labels for
external alarm
cables
MN
M: Equipment rows from
front to back are numbered
from A to Z.
N: Equipment columns from
left to right are numbered
from 01 to 99.
Labels for
network cables
MN-B-C-D
MN-Z
A label on the loaded
cabinet side that contains
information about the
position of the cable on
the power distribution
cabinet.
To:
A01 48V2
B08
To:
B03 48V2
To:
A01
- - - -
- - - -
A label on the power
distribution cabinet side that
contains information about
the position of the cable on
the loaded cabinet side.
A01-03-10-05: indicates that one end of the network
cable is connected to Huawei equipment, specifically,
to network port 5 in slot 10 of subrack 03 in the
cabinet in row A and column 01 in the
telecommunications room.
B02-03-12: indicates that the other end of the
network cable is connected to the terminal
equipment, specifically, to network port 12 in subrack
03 in the cabinet in row B and column 02 in the
telecommunications room. No slot number is
available.
MN: cabinet number
B: subrack number
C: physical slot
number
D: network port
number
Z: position number
To:
B02
- - - -
- - - -
03 12
A01 03 10 05