Item Description Default
Value
Value Range
Voltage Species the battery
equalized charging voltage.
The parameter is
congurable in any mode.
2.35 V/cell 2.33–2.40 V/cell
Max. time Species the maximum
equalized charging time. The
parameter is congurable
in any mode.
960
minutes
600–999
minutes
Figure 5-37 Equalized Charge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Table 5-28 Equalized Charge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item
Description Default
Value
Value Range
Equalized
charging
Species whether to enable
battery equalized charging.
The parameter is
congurable in any mode.
Enabled Disabled,
Enabled
Time
interval
Set the interval for equalized
charging. The parameter is
congurable in any mode.
60 days 30–180 days
Voltage Species the battery
equalized charging voltage.
The parameter is
congurable in any mode.
2.35 V/cell 2.33–2.40 V/cell
Max.
current
Set the maximum equalized
charging current. The
parameter is congurable
in any mode.
2.0 A Standard
backup time
model: 1.0–2.0
A
Long backup
time model:
1.0–4.0 A
Max. time Species the maximum
equalized charging time. The
parameter is congurable
in any mode.
960
minutes
600–999
minutes
UPS2000-G-(6 kVA–20 kVA)