Item Description Default Value Value Range
Intelli.
Hibernatio
n
When it is set to Enabled,
the intelligent battery
hibernation function is
enabled. The parameter is
congurable in any mode.
Disabled Disabled,
Enabled
Over
temp.
thres.
Species an alarm threshold
for battery overtemperature.
The parameter is
congurable in any mode.
50°C 45–55°C
Under
temp.
thres.
Species an alarm threshold
for battery
undertemperature. The
parameter is congurable
in any mode.
–5°C –30°C to +5°C
Over
current
thres.
Set an alarm threshold for
battery overcurrent. The
parameter is congurable
in any mode.
Note: The overcurrent alarm
threshold can be set only
for the UPS2000-G-15
kVA/20 kVA.
Standard
backup time
model: 3.0 A
Long backup
time model:
6.0 A
Standard
backup time
model: 2.0–4.0
A
Long backup
time model:
4.0–8.0 A
Equalized Charge
Figure 5-36 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Table 5-27 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item
Description Default
Value
Value Range
Equalized
charging
Species whether to enable
battery equalized charging.
The parameter is
congurable in any mode.
Enabled Disabled,
Enabled
Time
interval
Set the interval for equalized
charging. The parameter is
congurable in any mode.
60 days 30–180 days
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 99