Item Description Default Value Value Range
Intelli.
Hibernatio
n
When it is set to Enabled,
the intelligent battery
hibernation function is
enabled. The parameter is
congurable in any mode.
Disabled Disabled,
Enabled
Over
temp.
thres.
Species an alarm threshold
for battery overtemperature.
The parameter is
congurable in any mode.
50°C 45–55°C
Under
temp.
thres.
Species an alarm threshold
for battery
undertemperature. The
parameter is congurable
in any mode.
–5°C –30°C to +5°C
Over
current
thres.
Set an alarm threshold for
battery overcurrent. The
parameter is congurable
in any mode.
Note: The overcurrent alarm
threshold can be set only
for the UPS2000-G-15
kVA/20 kVA.
Standard
backup time
model: 3.0 A
Long backup
time model:
6.0 A
Standard
backup time
model: 2.0–4.0
A
Long backup
time model:
4.0–8.0 A
● Equalized Charge
Figure 5-36 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Table 5-27 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item
Description Default
Value
Value Range
Equalized
charging
Species whether to enable
battery equalized charging.
The parameter is
congurable in any mode.
Enabled Disabled,
Enabled
Time
interval
Set the interval for equalized
charging. The parameter is
congurable in any mode.
60 days 30–180 days
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 99