NO TE
The battery sharing setting is available only for the UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01. Battery sharing is enabled for the UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL by default.
Figure 5-35 Basic screen (UPS2000-G-6KRTS/UPS2000-G-10KRTS/UPS2000-
G-15KRTL/UPS2000-G-20KRTL)
Table 5-26 Basic screen (UPS2000-G-6KRTS/UPS2000-G-10KRTS/UPS2000-
G-15KRTL/UPS2000-G-20KRTL)
Item Description Default Value Value Range
Positive
(Negative
) batteries
Set the number of batteries.
When the number of
batteries
N
is less than 20,
the system output power is
derated by
N
/20 in battery
mode. The parameter is
congurable in non-
battery mode or non-
battery ECO mode. You
need to set the number of
batteries on the UPS2000-
G-6 kVA/10 kVA, and set
two battery strings (positive
and negative) on the
UPS2000-G-15 kVA/20 kVA.
0 16–20
Battery
capacity
Set the battery capacity.
This parameter indicates the
sum of all battery
capacities. Set the
parameters based on the
actual battery capacity. The
parameter is congurable
in non-battery mode or
non-battery ECO mode.
6 kVA standard
backup time
model: 7 Ah
6 kVA long
backup time
model: 40 Ah
10 kVA
standard
backup time
model: 9 Ah
10 kVA long
backup time
model: 65 Ah
15 kVA/20 kVA
long backup
time model: 65
Ah
7–1000 Ah
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 98