Table 5-25 Basic screen (UPS2000-G-15KRTL-01/UPS2000-G-20KRTL-01)
Item Description Default Value Value Range
Positive
(Negative)
batteries
Set the number of batteries.
When the number of
batteries
N
is less than 20,
the system output power is
derated by
N
/20 in battery
mode. The parameter is
congurable in non-
battery mode or non-
battery ECO mode.
0 16–20
Battery
capacity
Set the battery capacity.
This parameter indicates
the sum of all battery
capacities. Set the
parameters based on the
actual battery capacity. The
parameter is congurable
in non-battery mode or
non-battery ECO mode.
65 Ah 7–1000 Ah
Intelli.
Hibernatio
n
When it is set to Enabled,
the intelligent battery
hibernation function is
enabled. The parameter is
congurable in any mode.
Disabled Disabled,
Enabled
Over
temp.
thres.
Species an alarm
threshold for battery
overtemperature. The
parameter is congurable
in any mode.
50°C 45–55°C
Under
temp.
thres.
Species an alarm
threshold for battery
undertemperature. The
parameter is congurable
in any mode.
–5°C –30°C to +5°C
Charge
curr. limit
Species the charge current
limit. The parameter is
congurable in any mode.
2.0 A 1.0–4.0 A
Over
current
thres.
Set an alarm threshold for
battery overcurrent. The
parameter is congurable
in any mode.
6.0 A 4.0–8.0 A
Battery
string
sharing
Specify whether battery
string sharing is supported
in a parallel system.
Disabled Disabled,
Enabled
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 97