Table 5-25 Basic screen (UPS2000-G-15KRTL-01/UPS2000-G-20KRTL-01)
Item Description Default Value Value Range
Positive
(Negative)
batteries
Set the number of batteries.
When the number of
batteries
N
is less than 20,
the system output power is
derated by
N
/20 in battery
mode. The parameter is
congurable in non-
battery mode or non-
battery ECO mode.
0 16–20
Battery
capacity
Set the battery capacity.
This parameter indicates
the sum of all battery
capacities. Set the
parameters based on the
actual battery capacity. The
parameter is congurable
in non-battery mode or
non-battery ECO mode.
65 Ah 7–1000 Ah
Intelli.
Hibernatio
n
When it is set to Enabled,
the intelligent battery
hibernation function is
enabled. The parameter is
congurable in any mode.
Disabled Disabled,
Enabled
Over
temp.
thres.
Species an alarm
threshold for battery
overtemperature. The
parameter is congurable
in any mode.
50°C 45–55°C
Under
temp.
thres.
Species an alarm
threshold for battery
undertemperature. The
parameter is congurable
in any mode.
–5°C –30°C to +5°C
Charge
curr. limit
Species the charge current
limit. The parameter is
congurable in any mode.
2.0 A 1.0–4.0 A
Over
current
thres.
Set an alarm threshold for
battery overcurrent. The
parameter is congurable
in any mode.
6.0 A 4.0–8.0 A
Battery
string
sharing
Specify whether battery
string sharing is supported
in a parallel system.
Disabled Disabled,
Enabled
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 97