Item Description Default
Value
Value Range
Bat
mod
e
shut
dela
y
After the UPS transfers to
battery mode, the UPS shuts
down when the time
reaches the value of this
parameter. If this parameter
is set to 0S, the shutdown
delay function is disabled. If
the delay time is set to
other values, ensure that
backup time is greater than
shutdown delay time of
battery mode. Otherwise,
the power supply to loads
may be disconnected. The
parameter is congurable
in non-battery mode or
non-battery ECO mode.
NOTE
If the mains input and
bypass input use the same
power source, the system
powers o when the
shutdown delay in battery
mode reaches the preset
value. If the mains input
and bypass input use
dierent power sources,
the system transfers to
bypass mode when the
shutdown delay in battery
mode reaches the preset
value.
The Bat mode shut delay
parameter is not
synchronized in a parallel
system. In a parallel
system, set this parameter
to the same value for
dierent UPSs.
0s
0–600s
The value interval is
30s. For example, the
value can be 0s, 30s,
60s, and 90s.
Figure 5-40 Discharge Parameters screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel