Table 5-31 Discharge Parameters screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item Description Default
Value
Value Range
Max.
time
Species the maximum
discharge time. When the
discharge time reaches this
value, the system powers
o. If this parameter is set
to 0, the discharge time is
not limited. The parameter
is congurable in non-
battery mode or non-
battery ECO mode.
NOTE
● If you expect the battery
discharge time to be
greater than 24 hours, set
the parameter to <cf
id="Bold">0Hour</cf>.
Otherwise, the system may
power o.
● If you set the parameter to
0Hour, the battery may
remain in the small-current
discharge state according
to the proportion of the
battery capacity to the load
power, which aects the
battery lifespan.
16 hours
0–24 hours
EOD
mod
e
Determine the power
backup time. The
parameter is congurable
in non-battery mode or
non-battery ECO mode.
Backup time rst: The
system runtime is
preferentially ensured to
prolong the running of key
services and the backup
time is long.
Batt. protect rst: Batteries
are protected rst to
prolong the battery lifespan.
Backup
time rst
Backup power rst,
Batt. protect rst,
Balance mode
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 104