Table 5-31 Discharge Parameters screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item Description Default
Value
Value Range
Max.
time
Species the maximum
discharge time. When the
discharge time reaches this
value, the system powers
o. If this parameter is set
to 0, the discharge time is
not limited. The parameter
is congurable in non-
battery mode or non-
battery ECO mode.
NOTE
If you expect the battery
discharge time to be
greater than 24 hours, set
the parameter to <cf
id="Bold">0Hour</cf>.
Otherwise, the system may
power o.
If you set the parameter to
0Hour, the battery may
remain in the small-current
discharge state according
to the proportion of the
battery capacity to the load
power, which aects the
battery lifespan.
16 hours
0–24 hours
EOD
mod
e
Determine the power
backup time. The
parameter is congurable
in non-battery mode or
non-battery ECO mode.
Backup time rst: The
system runtime is
preferentially ensured to
prolong the running of key
services and the backup
time is long.
Batt. protect rst: Batteries
are protected rst to
prolong the battery lifespan.
Backup
time rst
Backup power rst,
Batt. protect rst,
Balance mode
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 104