Item Description Default
Value
Value Range
EOD
auto
-
start
Determine whether to
automatically start inverter
output after the mains
becomes normal after EOD.
This parameter is
congurable only after the
inverter is shut down.
Enabled Disabled, Enabled
Shut
dow
n
dela
y
After the UPS transfers to
battery mode, the UPS shuts
down when the time
reaches the value of this
parameter. If this parameter
is set to 0S, the shutdown
delay function is disabled. If
the delay time is set to
other values, ensure that
backup time is greater than
shutdown delay time of
battery mode. Otherwise,
the power supply to loads
may be disconnected. The
parameter is congurable
in non-battery mode or
non-battery ECO mode.
NOTE
● If the mains input and
bypass input use the same
power source, the system
powers o when the
shutdown delay in battery
mode reaches the preset
value. If the mains input
and bypass input use
dierent power sources,
the system transfers to
bypass mode when the
shutdown delay in battery
mode reaches the preset
value.
● The Bat mode shut delay
parameter is not
synchronized in a parallel
system. In a parallel
system, set this parameter
to the same value for
dierent UPSs.
0s
0–600s
The value interval is
30s. For example, the
value can be 0s, 30s,
60s, and 90s.
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 105