Figure 5-41 Shallow Discharge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Table 5-35 Shallow Discharge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item Description Default
Value
Valu
e
Rang
e
Timed
shallow
discharg
e test
Species whether to enable the scheduled
shallow discharge test. If this parameter is
set to Enable, the system automatically
performs a shallow discharge test when
the test interval arrives and the system
meets the shallow discharge conditions.
The parameter is congurable in any
mode.
Disabled Disab
led,
Enabl
ed
Time
interval
Set the interval for shallow discharge
tests. The parameter is congurable in
any mode.
60 days 30–
90
days
Discharg
e ratio
Species the proportion of the discharge
capacity to the total discharge capacity.
The parameter is congurable in any
mode.
20% 10%–
50%
Figure 5-42 Shallow Discharge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 107