Figure 5-41 Shallow Discharge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Table 5-35 Shallow Discharge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item Description Default
Value
Valu
e
Rang
e
Timed
shallow
discharg
e test
Species whether to enable the scheduled
shallow discharge test. If this parameter is
set to Enable, the system automatically
performs a shallow discharge test when
the test interval arrives and the system
meets the shallow discharge conditions.
The parameter is congurable in any
mode.
Disabled Disab
led,
Enabl
ed
Time
interval
Set the interval for shallow discharge
tests. The parameter is congurable in
any mode.
60 days 30–
90
days
Discharg
e ratio
Species the proportion of the discharge
capacity to the total discharge capacity.
The parameter is congurable in any
mode.
20% 10%–
50%
Figure 5-42 Shallow Discharge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 107