3.4.2 Configure
The FireTracer uses many set-up parameters, and is shipped with default values. The Configuration Mode allows changes to be made.
Below is a list of user-settable parameters, and their Factory Default values. The Parameter UP and Down buttons navigate through the
list; the Value UP and DOWN buttons change the value. The ENTER button saves the new value, and moves to the next parameter.
To Enter Configuration Mode:
1 Press MAIN MENU to enter the Main Menu list from Normal display mode
2 Use Parameter UP & DOWN buttons to reach CONFIGURE
3 Press ENTER
4 Enter Level 1 code or above
Parameter Range Factory Default
OPCODE Operator Function Access Code 0 - 999 0
ENDSCTR End Sector (number of sectors used) 1-default 4, 6, 8 or 15
DENSLOG Log of density change 0.01 – 20.00 0.02
F2LTCH Fire 2 Latch 0 or 1 1
F1LTCH Fire 1 Latch 0 or 1 1
ACTLTCH Action Latch 0 or 1 1
ALTLTCH Alert Latch 0 or 1 1
TRCLTCH Trace Latch 0 or 1 1
FLTLTCH Fault Latch 0 or 1 1
TRCRLY Trace Relay 1 0 or 1 0
REFCOMP Reference Compensation 0 - 5% 2.00%
REFDEL Reference Delay 5 - 60s 15s
FLOWDEL Flow Fault Delay 1 - 60s 5s
FLOWHI Flow High Limit 0 - 200% 150%
FLOWLO Flow Low Limit 0 - 200% 50%
FLOWLOG Log of flow change 0.0 – 200.0 5.0
SETFAN Set Fan Speed 2 to 10 5
STANDBY Battery Charger 0 or 1 0
PWRDEL a.c. supply fail delay 1 - 1000s 10s
BUZZER Internal Sounder Enable 0 or 1 1
BEACON Beacon Enable 0 or 1 1
ADDRESS RS485 Address 0 - 30 31 (off)
TESTTIM Time between automatic scans 1 – 30 mins 20
MINDWELL Rotary valve dwell time 0 – 60s 0
GAINX See description 1 -100 1
MODULE1 Set Module 1 usage
MODULE2 Set Module 2 usage
MODULE3 Set Module 3 usage
MODULE4 Set Module 4 usage
MODULE5 Set Module 5 usage
SC_DEL Suppression Control Delay 0-120 60
NIGHSTART Night Start time (Hour in 24 format) 12 – 23 12
NIGHSTOP Night Stop time (Hour in 24 format) 0 – 12 12
Notes:
1 The Alert Relay is used as a Trace Relay.
2 Avoid setting to values already defined for Level 1 or 2 Access Codes.
3 When Standby is set to 1, the panel display will extinguish if the AC mains supply is removed.
To revert all Configuration parameters to their default values go to MAIN MENU: LOAD DEFAULTS and press ENTER (level 2 Access Code
required). The Unit will restart with default parameters.