3.5.2 8 Channel 4-20mA Output Module
May be used for retransmission of Flow, Smoke or Gas levels
Number of analogue current outputs 8
Maximum output voltage 20 volts
Output current 4 - 20mA (optionally 0 - 20mA)
Resolution 16 bits
Maximum Integral Nonlinearity ±0.012%
Maximum Offset ±0.05%
Maximum total output error ±0.15%
Output update rate 1 per second; all 8 outputs updated
synchronously
Fault reporting Detects a high load resistance (e.g. an
open circuit) on any output.
N.B. Unused outputs must have a load connected; otherwise the open circuit will be seen as a fault.
Anything from 0R to 500R is suitable.
ANALOG OUTPUT MODULE
123 4
CHANNEL CHANNEL CHANNEL CHANNEL
SECTORCONFIG
FLOW X
SMOKE X
GAS 1
GAS 2
FLOW X
SMOKE X
GAS 1
GAS 2
FLOW X
SMOKE X
GAS 1
GAS 2
FLOW X
SMOKE X
GAS 1
GAS 2
FLOW X
SMOKE X
GAS 1
GAS 2
FT1/ET1
FT1/ET1
ET1
ET1
FT4/ET4
FT4/ET4
ET4
ET4
FT6/ET6
FT6/ET6
ET6
ET6
FT8/ET8
FT8/ET8
ET8
ET8
FT15/ET15
FT15/ET15
ET15
ET15
UNIT SECTOR SECTOR SECTOR
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
1 2 3 4
1 2 3 4
1 2 3 4
D
D
A
A
D
D
A
A
D
D
A
A
D
D
A
A
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
D
D
A
A
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
D
D
A
A
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
D
D
A
A
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
D
D
A
A
D
D
A
A
D
D
A
A
D
D
A
A
D
D
A
A
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 D
9 10 11 12 13 14 15 D
9 10 11 12 13 14 15 A
9 10 11 12 13 14 15 A
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 D
9 10 11 12 13 14 15 D
9 10 11 12 13 14 15 A
9 10 11 12 13 14 15 A
D = DETECTOR READINGS (FLOW X: DETECTOR FLOW)
FT/ET 8 ONLY: IF END SECTOR IS SET TO LESS THAN 8, CHANNEL 8 WILL BE EITHER THE DETECTOR
READING (FLOW X or SMOKE X) OR
"ALL SECTORS" READING (GAS1 or GAS2)
(SMOKE X: REAL TIME DENSITY)
A = "ALL SECTORS" READING (GAS1 or GAS2)
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
+
-
-
-
-
-
-
-
-
+
+
+
+
+
+
+
Installation (refer to table below)
Scroll To Set Value to
SETUP (MODULE n) Set to ANOUT 8
CONFIGURE (MOD n) According to Table e.g. SMOKE X
(GAIN X) Applies to Smoke only:
e.g. Set to 10 for 20mA = 2%
To Access SETUP: <MENU> (or<CODE>)
PARAMETER <UP> / <DOWN> ---> “SETUP”
ENTER CODE 693
To Access CONFIG: <MENU> (or<CODE>)
PARAMETER <UP> / <DOWN> ---> CONFIGURE
MODULES ARE NUMBERED
1 TO 5, LEFT TO RIGHT