EasyManua.ls Logo

icam FT6 - Installation Procedures

Default Icon
47 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
2 INSTALLATION
The units should be installed in accordance with the following installation instructions and in a manner acceptable to the local inspection
authority having jurisdiction. The units are also intended to be installed in accordance with NFPA No. 72 Standard - titled “National Fire
Alarm Code”.
Careful consideration should be given to the mounting location of the FireTracer unit to ensure that:
It is positioned at an accessible height to facilitate commissioning, routine testing and maintenance.
It is positioned in an area where the exhaust air pipe will remain clear of obstacles at all times.
It is not installed above a heat source such as a radiator or in direct air flow source such as Air Conditioners.
It will be secure and free from operation by unauthorised personnel.
The following steps should be carried out in order to correctly install the FireTracer system.
The FireTracer back box should be securely fitted to a suitable wall or support using the three points shown in the fixing diagrams
in section 2.1. M6 or M8 screws are suitable.
The cables for the power supply, battery and any I/O modules should be fitted.
The pipe network is fitted to the system. For details on how to design and install a pipe network, see Pipe Installation Manual
(ICAM Part No. 09-0003-10)
2.1 Mounting Diagrams
Pico Fixin
g
s

Related product manuals