25
ADDRESS
This is the unit’s RS485 address, required when using ICAMnet. The range is 0 to 30; a value of 31 disables RS485 comms. The
default setting is 31 (off). Note that if the display panel is used remotely, communication to it is by means of this RS485 comms
port, and the ADDRESS setting is not used.
TESTTIM
Set in minutes. If no rotary valve movement has been triggered within this time period then an automatic scan will be initiated.
(Rotary valve systems only).
MINDWELL
Used for rotary valve movement control. Determines the minimum time in seconds that the valve will remain stationary between
sectors. (Rotary valve systems only).
GAINX
Used to re-transmit the density with the 8 channel 4-20mA output module.
MOD1, MOD2, MOD3, MOD4, MOD5
Some module types may be used in different ways. MOD1 to MOD5 sets the usage of these modules. See under the specific I/O
module section.
SC_DEL
The time period the alarm must be sustained before the suppression system begins.
NIGHSTART, NIGHSTOP
The time in hours, on a 24 hour basis, at which the values change from day to night or back again. The default value for both is
12, at this value only the day values are applicable
.