FT9Y-B1378 5-45
5: S
PECIAL
F
UNCTIONS
5. To suspend the forced I/O, click the Start/Suspend Force button .
The forced inputs or outputs remain designated until the forced I/O designation is released.
6. To release the forced I/O designation, click the Force Release button .
Now input I0 works as a normal input.
Note: Make sure that all the forced inputs and outputs are released when the test using the forced I/O function is finished. Select Delete All from
the right click menu in the Forced I/O List dialog box to release all the forced inputs and outputs at once.
Even though I0 is designated,
forced I/O is suspended and
actual input status is read to the
SmartAXIS.
Input I0 is released from the
forced I/O designation. Even
when forced I/O is enabled, actual
input status is read to the
SmartAXIS.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC FT1A Series and is the answer not in the manual?

IDEC FT1A Series Specifications

General IconGeneral
Programming SoftwareWindLDR
TypeProgrammable Logic Controller (PLC)
DisplayLCD (varies by model)
Communication PortsRS232C/RS485 (built-in), USB (programming), Ethernet (optional)
DimensionsVaries by model
WeightVaries by model
ModelFT1A Series

Related product manuals