Page #165 background imageLoading...
Page #165 background image
S
MART
AXIS P
RO
/L
ITE
U
SER
'
S
M
ANUAL
FT9Y-B1378 6-1
6: HMI FUNCTION
Introduction
You can run and stop the user program, monitor device values, and modify settings on the SmartAXIS Pro by using the LCD and
operation buttons on the SmartAXIS. This chapter describes how to modify the user program and device values with the operation
buttons.
Function Description
The following functions can be used with SmartAXIS button operations.
Initial Screen
The screen below is displayed when the SmartAXIS is purchased and first turned on.
The default menu language is English. To switch the menu language to Japanese, see "Changing the Menu Language" on page 6-
8.
Type Function Description
Run/stop
operation
Switching run/stop
The program running state (run/stop) can be changed with the
operation buttons on the SmartAXIS.
Edit Program
Confirming/Clearing changed timer/
counter preset values
Change timer/counter preset values or writes them to the user
program in the ROM.
Configurations
Environment
settings
Slave Number/
Message Scroll/Blink
Menu Language/
LCD backlight ON time
Some of the function area settings (slave number, message scroll
speed, scroll unit, blinking speed, and LCD backlight ON time) can be
modified.
The system menu language can also be changed.
Calendar/Clock Configures the calendar/clock of the SmartAXIS internal clock.
Monitors
Device Monitor Displays/modifies the specified device values.
Program Monitor
Displays the ladder program.
The on/off state of bit devices can be changed. This is only enabled
when ladder program is selected as the programming language.
Status Monitor
Displays the system software version, operating status, scan time, and
protection status.
Error Monitor Enables you to check errors that have occurred on the SmartAXIS.
Message display Message display
Displays messages with pre-configured formats on the SmartAXIS LCD
using the MSG instruction/FB.
Memory Cartridge
Uploading user program
The user program in the SmartAXIS can be transferred to the memory
cartridge.
Downloading user program
The user program on the memory cartridge can be transferred to the
SmartAXIS.
SD memory card
Stop Access
Stops the access to the SD memory card in order to remove the SD
memory card from the SmartAXIS.
Format Formats the SD memory card.
Power turned on
Stopped
Standard screen
SmartAXIS
2000/JAN/01/SAT
00:00:00
Stopped
2000/JAN/01/SAT
00:00:00

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC FT1A Series and is the answer not in the manual?

IDEC FT1A Series Specifications

General IconGeneral
Programming SoftwareWindLDR
TypeProgrammable Logic Controller (PLC)
DisplayLCD (varies by model)
Communication PortsRS232C/RS485 (built-in), USB (programming), Ethernet (optional)
DimensionsVaries by model
WeightVaries by model
ModelFT1A Series