TA-SCOPE
42
Dp Sensor Battery Indicator
The DpS-Visio have a LED showing fixed or flashing green, orange or red light depending on battery status and
remaining capacity.
Red light Less than 30% battery capacity remaining
Orange light Less than 70% battery capacity remaining
Green light More than 70% battery capacity remaining
Fixed light Charging completed
Flashing light 1 sec. Charging in progress
Flashing light 2 sec. On battery or Dp Sensor connected to Handheld for additional power supply
Flashing light 9 sec.
(for Dp Sensor only)
Dp Sensor in sleep mode whilst logging is in progress. Press
during 1 second to reactivate the
Dp Sensor.
Filter Cleaning
Filters in the measuring hoses protect the Dp Sensor from dirt and particles in the fluid running in the hydronic
system.
Wear of the filter depends on usage, change when required to maintain optimum accuracy. A set of spare filters is
delivered with the TA-SCOPE and can also be ordered as an accessory.
Clean the filter frequently, preferably after each session.
Use the Allen key, 3 mm, provided in the TA-SCOPE case, to remove the filter holder (1), washer (2), O-ring (3)
and filter (4). Release and wash the filter.
Calibration Certificates
Calibration certificates for the TA-SCOPE Dp Sensor and Digital Temperature Sensor are issued after the delivery
control. The equipment used is traceable to national standards according to ISO 9001 or equivalent.
The frequency of calibration depends upon instrument usage and requirements according to corporate standards.
IMI Hydronic Engineering recommends regular calibration of the Dp sensor and Digital Temperature Sensor on an
annual basis to ensure optimum performance.
1
3
4
2
Instrument Care & Service