EasyManua.ls Logo

Immergas VICTRIX OMNIA - Page 77

Immergas VICTRIX OMNIA
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
77
INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
Id
Parameter
Parameter Description Range Default
Value
value
G Gas type
Denes operation with methane gas nG
nG
Denes operation with LPG gas LG
Denes operation with propane air gas
(can be activated by means of a special menu)
AP
In the event of an alteration, anomaly “E62” appears and complete calibration is required.
Id
Parameter
Parameter Description Range Default
Value
value
n Boiler model Dene the boiler model 0 ÷ 1
0 = Victrix
Omnia
1 = Not used
In the event of an alteration, anomaly “E62” appears and complete calibration is required.
Id
Parameter
Parameter Description Range Default
Value
value
S0 Min output
e P.C.B. denes the operating mode and the boiler output
according to the combination of several parameters. e
proper operating output of the appliance is dened
according to the combination of the parameters of menus
“n” and “F. For this reason it is recommended not to alter the
parameters of this menu in order not to compromise the
proper operation of the boiler.
750 ÷ 1700
rpm
1300
(nG/LG)
S1 Max output S0 ÷ 6900 rpm
6200
(nG/LG)
S2 Ignition output
2000 ÷ 4500
rpm
3200
(nG/LG)
In the event of an alteration, anomaly “E62” appears and complete calibration is required.
Id
Parameter
Parameter Description Range Default
Value
value
P0 DHW max
Denes the maximum heat output percentage of the boiler
during the D.H.W. phase compared to the maximum heat
output available
0 - 99 % 99 %
P1 Min output
Denes the minimum heat output percentage of the boiler
compared to the minimum heat output available
0 - P2 0 %
P2
Central heating
max
Denes the maximum heat output percentage of the boiler
during the central heating mode compared to the maximum
heat output available
0 - 99 % 79 %
P3 - Not used - -
P4 - Not used - -
P5 - Not used - -
P6
Pump function-
ing
e pump can function in two ways.
0 intermittent: in winter "mode" the circulator is managed by
the room thermostat or by the remote control.
1 continuous: in "winter" mode the circulator is always
powered and is therefore always in operation
0 - 1 0
P7
External probe
correction
If the reading of the external probe is not correct it is possible
to correct it in order to compensate any environmental
factors.
-9 ÷ 9 K 0
P8 - Not used - -

Table of Contents

Other manuals for Immergas VICTRIX OMNIA

Related product manuals