52 Programming the extinguishant module
Installation and programming manual
12.3.3 Signals that activate the point
Manual
extinguish
Same as MAN-EXT input.
EXAMPLE: A point connected to a Start-extinction button located inside the
protected environment.
Lock
extinguish
Same as STOP-EXT input
EXAMPLE: A point connected to a Stop-extinction button located inside the
protected environment.
Monitor
restore
YES The signal can be reset (e.g.: by releasing the button).
NO The signal will persist until RESET button on the panel is pressed.
Output ------------- The point is not activated by any signal.
Extinguish Point activated at the same time as the RELEASED output programmed as
“Extinguish”.
Pre-
extinguish
Point activated at the same time as the PRE-EXT output.
Confirm
extinguish
Point activated by a “Confirm extinguish” input point.
Lock
extinguish
Point activated by the activation of “Lock extinguish” input point or by the STOP-
EXT input.
Silenceable YES The output can be silenced.
NO The output will remain active until the RESET button on the panel is pressed.
Duration Length of time the outputs will remain active.