58 Maintenance
Installation and programming manual
After maintenance or on first startup, it may be necessary to force a point output or detector LED. For
example, the On status of a detector LED allows fast identification of the detector location on the protected
premises.
1. Press Ok to activate/deactivate the LED or output
2. Press SorT to go to the adjacent point or zone.
16.7 Set the date for the next maintenance session
From the panel:<key>, Maintenance, Maintenance, Ok
If you have set the date of the next maintenance session, the system will signal a fault event on the
specified date. Only a new date, selected via this menu, will clear this fault signal.
16.8 Loop Diagnostics
From panel:<key>, Maintenance, Diagnostic
This menu will allow you to carry out diagnostics on all the smoke detectors connected to the loop. After
the diagnostics phase, the panel will show the maximum level of dust detected, the detector concerned and
the average dust level of all the detectors.
The loop diagnostics and that of each of its point can be done via FireGenius software supplied with the
EITK1000 driver (refer to Appendix A - Enea series devices). This software, in addition to allowing use of
the driver via PC, offers a graphic interface which provides a detailed view of the entire loop.
For a detailed description, refer to the respective user manual.
Point 123
j
<point123>
Output
ON
l
Maint. Fault
dd/mm/yy hh:mm
Monday
Dust
Average xxx%
Maximum xxx%
Point nnn