-18-
3 Product Specications
AC800 Series Intelligent Machine Controller Hardware User Guide
3.2 Environmental Specications
The environmental specications of the controller are shown in the following table:
Item Parameter Type Operation Transport Storage
Environmental 
data 
(IEC60721-3)
Class IE33  IE22 IE12
Temperature -5–55℃ -40–70℃ -25–70℃
Humidity 10–95%, no-condensation
Vibration
Frequency 5-200Hz
2M2 1M2
Displacement
3.5 mm (direct 
installation) (< 8.4 Hz)
Acceleration
1 g (direct installation) 
(> 8.4 Hz)
Direction 3 axial directions
Impact (collision)
15 g, 11 ms, half 
sine wave, 3 axial 
directions
Altitude/air pressure 0–2000 m 0–3000 m ( ≤ 70 kPa)
3.3 EMC Specications
The EMC specications of the controller are shown in the following table:
No. Item Standard Description
1
Conducted emission 
Power supply terminal
IEC61131-2:2007 Class A
2
Radiated emission
Controller
IEC61131-2:2007 Class A
3 ESD
IEC61131-2:2007
IEC 61000-4-2: 2002
±6 kV, (contact discharge)
±8 kV, (air discharge)
4 RS: Radiated susceptibility
IEC61131-2:2007
IEC 61000-4-3: 2002
80 - 1000MHz 10V/m,
1710M-1784M 10V/m
1880M-1960 M 10V/m
5
EFT/Burst,
DC Power supply terminal
IEC61131-2:2007
IEC 61000-4-4: 2006
±2 kV, direct injection
(5/50ns,5/100kHz)
6
EFT/Burst,
Communication and signal 
port
IEC61131-2:2007
IEC 61000-4-4: 2006
±2 kV, capacitive coupling 
clamp
(5/50ns,5/100kHz)
7
CS: Conducted susceptibility
DC Power supply terminal
IEC61131-2:2007
IEC 61000-4-6: 2003
(0.15-80)MHz, 
(1kHz, AM 80%)
10V, CDN
8
CS: conducted susceptibility
Communication and signal 
port
IEC61131-2:2007
IEC 61000-4-6: 2003
(0.15-80)MHz, 
(1kHz, AM 80%)
10 V, electromagnetic clamp
9
Surge
DC Power supply terminal
IEC61131-2:2007
IEC 61000-4-5: 1995
±1 kV (line to ground)
±0.5 kV (line to line)
10
Surge
Communication and signal 
port
IEC61131-2:2007
IEC 61000-4-5: 1995
±1 kV (line to ground)