6.2 Power-o
safety precautions
◆ The AC800 series controller will continue to operate normally for a certain period of time when an
instantaneous power failure occurs, so it may receive error signals from external devices aected by
the instantaneous power
failure.
◆ Take fail-safe measures externally and monitor the power supply voltage on the external device side
as necessary, and also take safety measures in the user
program.
See the table below.
Power-o voltage
UPS Code Power input Power-o voltage
72030012 DC24V Below 22.5 V
Power Type
Power Type Power-o evaluation time
Non-UPS Power o immediately
UPS 15 ms
6.2.1 Operation at Power-o
When a power failure occurs because the following power-o evaluation time is exceeded, the user
program is terminated. The PLC is stopped when the operations after power-o evaluation are performed
(see section 6.2.3).
Power Type Time before power-o
Non-UPS Power o immediately
UPS Above 15 ms