Display on
the
Operation
Panel
Display of
the Nixie
Tube
Fault
Description
Possible Causes Solution
large or the braking unit
is abnormal.
4. The acceleration curve
is too steep.
curve.
Err06 E06
Over-voltage
during
deceleration
1. The input voltage is
too high.
2. The value of the
braking resistor is too
large or the braking unit
is abnormal.
3. The deceleration
curve is too steep.
1. Adjust the input voltage.
2. Choose a proper braking
resistor.
3. Modify the parameters of the
curve.
Err07 E07
Overvoltage at
constant speed
1. The input voltage is
too high.
2. The value of the
braking resistor is too
large or the braking unit
is abnormal.
1. Adjust the input voltage.
2. Modify the parameters of the
curve.
Err09 E09
Under-voltage
protection
1. Instantaneous failure
of input power occurs.
2. The input voltage is
too low.
3. The drive board is
abnormal.
1. Eliminate external problems
such as wiring error.
2. Contact the agent or Inovance
for technical support.
Err10 E10
AC drive
overloaded
1. The brake circuit is
abnormal.
2. The load is too heavy.
1. Check the brake circuit and
power supply.
2. Reduce the load.
Err11 E11
Motor
overloaded
1. F9-01 is set
incorrectly.
2. The brake circuit is
abnormal.
3. The load is too heavy.
1. Modify the setting of F9-01.
2. Check the brake circuit and
power supply.
3. Reduce the load.
Err12 E12
Phase loss at
input side
1. The input power is
asymmetric.
2. The drive board is
abnormal.
1. Adjust the input power.
2. Contact the agent or Inovance
for technical support.
Err13 E13
Phase loss at
output side
1. The output cable of
the main circuit is loose.
2. The motor is
damaged.
1. Check the cabling.
2. Rectify faults of the motor.
Err14 E14
Module
overheated
1. The ambient
temperature is too high.
2. The fan is damaged.
3. The air filter is
blocked.
1. Reduce the ambient
temperature.
2. Clean the air filter.
3. Replace the fan.
Err15 E15
External device
fault
1. STOP is pressed in
non-operation panel
control mode.
2. The external fault
signal is input to the
multi-function DI
terminal.
1. Ensure that operations on the
operation panel are correct.
2. Check the setting of DI terminal
functions in group F4.
Err16 E16
Communication
fault
1. Connection of the
RS485 communication
cable is incorrect.
2. The parameters in
1. Check connection of the
communication cable.
2. Re-set the parameters in group
FD.
efesotomas
on.com