IS300 Series Servo Drive User Manual Appendix
- 79 -
Function
Code
Name Setting Range Min. Unit Default Property
F3-06 V/F voltage 2 0.0%–100.0% 0.1% 0.0% ★
F3-07 V/F frequency 3
0.00 Hz–rated motor
frequency
0.01 Hz 0.00 Hz ★
F3-08 V/F voltage 3 0.0%–100.0% 0.1% 0.0% ★
F3-09
V/F slip
compensation gain
0.0%–200.0% 0.1% 0.0% ☆
F3-10 AVR selection
0: Invalid
1: Valid in the whole
process
2: Invalid only during
deceleration
1 2 ☆
F3-11
V/F oscillation
suppression gain
0–100 1
Model
dependent
☆
Group F4: Input Terminals
F4-00
DI1 function
selection
0: No function
1: Forward RUN (FWD,
pump enabled)
2: Reverse RUN (REV)
3: Three-wire control
4: Forward JOG (FJOG)
5: Reverse JOG (RJOG)
6: Terminal UP
7: Terminal DOWN
8: Coast to stop
9: Fault reset (RESET)
10: RUN pause
11: External fault NO input
12: Multi-speed terminal 1
13: Multi-speed terminal 2
14: Multi-speed terminal 3
15: Multi-speed terminal 4
16: Acceleration/
Deceleration time selection
terminal 1
17: Acceleration/
Deceleration time selection
terminal 2
1 1 ★
F4-01
DI2 function
selection
1 0 ★
F4-02
DI3 function
selection
1 9 ★
F4-03
DI4 function
selection
1 0 ★