Appendix IS300 Series Servo Drive User Manual
- 86 -
Function
Code
Name Setting Range Min. Unit Default Property
F8-14
Action selection
when set
frequency below
frequency lower
limit
0: Run at frequency lower
limit
1: Stop
2: Run at zero speed
1 0
F8-15 Droop control 0.00–10.00 Hz 0.01 Hz 0.00 Hz
F8-16 Overmodulation
0: Disabled
1: Enabled
1 0
F8-17
Set accumulative
running time
0–65000 h 1 h 65000 h
F8-18
Startup protection
selection
0: Not protected
1: Protected
1 0
F8-19
Frequency
detection
value (FDT)
0.00 Hz–max. frequency
0.01 Hz 50.00 Hz
F8-20
Frequency
detection
hysteresis (FDT
hysteresis)
0.0%–100.0% (FDT level)
0.1% 5.0%
F8-21
Frequency
reaching detection
amplitude
0.00–100% (max.
frequency) 0.1% 0.0%
F8-22
Detection of short-
circuit to earth
protection upon
power-on
0: Disabled
1: Enabled
1 1
F8-23
Action selection
when the running
time is reached
0: Continue to run
1: Stop 1 0
Group F9: Fault and Protection
F9-00
Motor overload
protection
selection
0: Disabled
1: Enabled 1 1
F9-01
Motor overload
protection gain
0.20–10.00
0.01 1.00
F9-02
Motor overload
alarm coefcient
50%–100%
1% 80%
F9-03
Over-voltage stall
gain
0 (no stall overvoltage)
–100
1 0
F9-04
Over-voltage stall
protective voltage
120%–150% 1% 130%
F9-05
Over-current stall
gain
0–100 1 20