Mechanical Installation (T13 Models)
‑104‑
Figure 6‑2 Installing an expansion screw
6.5 Requirements on Foundation
1. Separate high‑voltage cables from low‑voltage cables by placing them on different
brackets. For failure to do so due to any restrictions, place the low‑voltage cables in
a completely enclosed metal pipe.
2. Ensure that the cable trench is non‑flammable, smooth, and well protected from
moisture, dust, and animals.
3. During foundation design, take the following factors into consideration: access
space in front of the cabinet, and wiring of power cables, actuating motor cables,
and system control cables. The cabinet comes with a cable trench or cable guide.
Separate power cables from signal cables. Failure to comply may affect the
operation of the AC drive. The following figure shows the routing and related
requirements.
Figure 6‑3 Foundation layout