Mechanical Installation (T1 to T9 Models)
‑63‑
4 Mechanical Installation (T1 to T9 Models)
4.1 Installation Method
T1 to T9 models support backplate mounting and through‑hole mounting.
4.2 Cabinet Design
4.2.1 Overview
Before installing the AC drive in the cabinet, design the cabinet to ensure sufficient
clearances for installation and heat dissipation. Take the following factors into
consideration:
● Cabinet clearances
● Mounting backplate
● Cabinet heat dissipation
4.2.2 Cabinet Clearance Requirements
For T1 to T9 models, install one AC drive above another. The following table lists the
minimum requirements for clearance between AC drives. Install an air guide plate on
each AC drive except for the top one.
Table 4–1 Minimum clearance for installing one AC drive above another
Item T1 to T4 T5 T6 T7 to T9
S1
≥ 100 mm ≥ 200 mm ≥ 200 mm ≥ 300 mm
S2
≥ 100 mm ≥ 200 mm ≥ 200 mm ≥ 300 mm
...
≥ 100 mm ≥ 200 mm ≥ 200 mm ≥ 300 mm
Sn
≥ 100 mm ≥ 200 mm ≥ 200 mm ≥ 300 mm