Mechanical Installation (T10 to T12 Models)
‑89‑
5 Mechanical Installation (T10 to T12 Models)
5.1 Installation Method
T10 to T12 models can be installed in a cabinet.
5.2 Installation Precautions
Before installation, install the bottom mounting bracket in and mount the guide
rails to the cabinet and provide the fixing beam for fixing the AC drive, with
mounting holes reserved in the fixing beam. Reserve the clearance in the cabinet
for connecting the copper busbar of the AC drive.
The guide rails and the four casters at the bottom of the AC drive cooperate to
help it come in or out of the cabinet. Align the casters with the guide rails before a
push or pull. To ensure safety, ensure two persons are there cooperating to pull or
push the AC drive.
Reserve sufficient clearance for heat dissipation, including the heat dissipation of
other equipment in the cabinet.
Ensure two persons are there cooperating to push the AC drive into or pull it out of
the cabinet. After the AC drive is in the cabinet, remove the cardboard from its air
outlet to avoid over‑temperature caused by failure to exhaust hot air inside.
When installing the AC drive in the cabinet, install an insulation barrier at the top
of the cabinet to prevent the exhaust air from circulating in the cabinet. Make sure
air intake vents are provided in the lower part of the cabinet door.
The cabinet is 2200 mm x 800 mm x 600 mm in size (including a ventilation top
cover 200 mm in height). To ensure installation of the cabinet, reserve extra space
for a cabinet base 100 mm in height.
When the AC drive is installed in an enclosed environment, such as a cabinet or
casing box, use a cooling fan or air conditioner to keep the temperature of the air
taken in below 50℃. Failure to comply may result in overheating or fire.
Cover the top of the AC drive with cloth or paper during installation to prevent
metal shavings, oil, and water from entering during drilling. Foreign objects
entering may cause malfunction of the AC drive. Remove the cloth or paper after
the installation is completed. Failure to comply may degrade ventilation and result
in unexpected heat.
Use a mounting bracket that is flame retardant, where appropriate.
For environments with metal dust, use a cabinet that can completely enclose the
AC drive to isolate the AC drive from metal dust. In this case, as much space as
possible should be provided in the fully sealed cabinet, and it is recommended
that the radiator be installed outside the cabinet.
Tighten all screws using the specified torque. Failure to comply may result in
electric shock or fire.