Mechanical Installation (T1 to T9 Models)
‑84‑
Step Description Diagram
3 Tighten two M4 x 12 SEMS screws onto the two
positions shown in ④.
4 Mount the cover.
Wiring
Use shielded cables for motor output. Use a grounding bracket to achieve all‑round
connection with the shield, and crimp the lead wire of the shield to the PE terminal.
The grounding bracket of cable shield is provided with a wire ferrule slot. Cover the
exposed shield with insulation tape above the wire ferrule. The following figure shows
the wiring.