Mechanical Installation (T10 to T12 Models)
‑91‑
AC Drive Model
Quantity of Fans
Total Airflow
(CFM)
Effective Area of
the Cabinet Air
Inlet (mm
2
)
Effective Area of
the Cabinet Air
Outlet (mm
2
)
T12 (400 kW)
3 796 47713 76341
T12 (450 kW)
3 796 47713 76341
Note:
CFM = 0.0283 m
3
/min
"Actual Effective Area" indicates through‑hole area.
Figure 5‑2 Forced ventilated cabinet (with fans on the top of the cabinet)