Electrical Installation
‑142‑
Str
uc
tur
e
Drive Model
Rated
Input
Current
(A)
R/S/T, U/V/W
Grounding Cable
Screw
Tightening
Torque
(N·m)
(lb.in)
Recom
mended
Cable
(AWG/
mil)
<2>
Recom
mended
Cable Lug
Recom
mended
Cable
(AWG/
mil)
<2>
Recommend
ed Cable Lug
T8
MD520‑4T75(B)
(S)
139.0
3/0
TLK95‑12
1/0
TLK50‑8
M12 (main
power)
35.0
(310.1)
M8
(grounding)
13.0
(115.2)
MD520‑
4T90(S)
164.0
3/0
TLK95‑12
1/0
TLK50‑8
M12 (main
power)
35.0
(310.1)
M8
(grounding)
13.0
(115.2)
MD520‑
4T110(S)
196.0 300 TLK150‑12
3/0
TLK95‑8
M12 (main
power)
35.0
(310.1)
M8
(grounding)
13.0
(115.2)
T9
MD520‑
4T132(S)
240.0
350 TLK185‑12
3/0
TLK95‑10
M12 (main
power)
35.0
(310.1)
M10
(grounding)
20
(117)
MD520‑
4T160(S)
287.0
450 TLK240‑12 250 TLK120‑10
M12 (main
power)
35.0
(310.1)
M10
(grounding)
20
(117)
T1
0
MD520‑
4T200(S) (‑L)
365.0 4x1/0 TLK50‑12 2x1/0 TLK50‑12 M12 35.0
(310.1)
MD520‑
4T220(S) (‑L)
410.0 4x1/0 TLK50‑12 2x1/0 TLK50‑12 M12 35.0
(310.1)
T1
1
MD520‑
4T250(S) (‑L)
441.0 4x1/0 TLK50‑12 2x1/0 TLK50‑12 M12 35.0
(310.1)
MD520‑
4T280(S) (‑L)
495.0 4x2/0 TLK70‑12 2x2/0 TLK70‑12 M12 35.0
(310.1)
T1
2
MD520‑
4T315(S) (‑L)
565.0 4x3/0 TLK95‑16 2x3/0 TLK95‑16 M16 85.0
(753.1)
MD520‑
4T355(S) (‑L)
617.0
4 x 250 TLK120‑16 2 x 250 TLK120‑16 M16
85.0
(753.1)
MD520‑
4T400(S) (‑L)
687.0
4 x 250 TLK120‑16 2 x 250 TLK120‑16 M16
85.0
(753.1)
T1
3
MD520‑
4T500(S)‑(A)
838.1 4x300kcmi
l
TLK150‑16 2x300kcmil TLK150‑16
M16
85.0
(753.1)
MD520‑
4T560(S)‑(A)
949.6 4x350kcmi
l
TLK185‑16 2x350kcmil TLK185‑16
M16
85.0
(753.1)
MD520‑
4T630(S)‑(A)
1043.5 4x400kcmi
l
TLK240‑16 2x400kcmil TLK240‑16
M16
85.0
(753.1)