Electrical Installation
‑141‑
Table 8–5 Cable selection (three‑phase 380 V to 480 V) (with UL certification)
Str
uc
tur
e
Drive Model
Rated
Input
Current
(A)
R/S/T, U/V/W
Grounding Cable
Screw
Tightening
Torque
(N·m)
(lb.in)
Recom
mended
Cable
(AWG/
mil)
<2>
Recom
mended
Cable Lug
Recom
mended
Cable
(AWG/
mil)
<2>
Recommend
ed Cable Lug
T1 MD520‑
4T0.4B(S)
1.8
16 TLK1.25‑4 18 TLK1.25‑4 M4
1.2
(10.6)
MD520‑
4T0.7B(S)
2.4
16 TLK1.25‑4 18 TLK1.25‑4 M4
1.2
(10.6)
MD520‑
4T1.1B(S)
3.7
16 TLK1.25‑4 18 TLK1.25‑4 M4
1.2
(10.6)
MD520‑
4T1.5B(S)
4.6
16 TLK1.25‑4 18 TLK1.25‑4 M4
1.2
(10.6)
MD520‑
4T2.2B(S)
6.3
16 TLK1.25‑4 18 TLK1.25‑4 M4
1.2
(10.6)
MD520‑
4T3.0B(S)
9.0
16 TLK1.25‑4 18 TLK1.25‑4 M4
1.2
(10.6)
T2 MD520‑
4T3.7B(S)
11.4 16 TLK1.25‐4 16 TLK1.25‐4 M4 1.2
(10.6)
MD520‑
4T5.5B(S)
16.7 14 TLK2‑4 14 TLK2‑4 M4 1.2
(10.6)
T3 MD520‑
4T7.5B(S)
21.9 12 TLK3.5‐5 12 TLK3.5‐5 M5 2.8
(24.8)
MD520‑
4T11B(S)
32.2 8 TLK10‑5 8 TLK10‑5 M5 2.8
(24.8)
T4 MD520‑
4T15B(S)
41.3 6 TLK16‑5 6 TLK16‑5 M5 2.8
(24.8)
T5 MD520‑
4T18.5(B) (S)‑
T
49.5 6 TLK16‑6 6 TLK16‑6 M6 4.8
(42.5)
MD520‑
4T18.5(B)(S)
49.5 6 TLK16‑6 6 TLK16‑6 M6 4.8
(42.5)
MD520‑4T22(B)
(S)‑T
59.0 4 TLK25‑6 6 TLK16‑6 M6 4.8
(42.5)
MD520‑4T22(B)
(S)
59.0 4 TLK25‑6 6 TLK16‑6 M6 4.8
(42.5)
T6 MD520‑4T30(B)
(S)
57.0 4 TLK25‑6 6 TLK16‑6 M6 4.8
(42.5)
MD520‑4T37(B)
(S)
69.0 2 TLK35‑6 6 TLK16‑6 M6 4.8
(42.5)
T7 MD520‑4T45(B)
(S)
89.0 2 TLK35‑8 6 TLK16‑8 M8 13.0
(115.2)
MD520‑4T55(B)
(S)
106.0 1/0 TLK50‑8 4 TLK25‑8 M8 13.0
(115.2)