Electrical Installation
‑169‑
● Wiring example when the internal 24 V is used
Note
EMC Requirements
■ To avoid short circuit between adjacent conductors, use shielded cables and connect
the shield to the protective ground. Alternatively, use flat cables and connect a ground
cable between adjacent signal conductors.
■ Use cables that contain twisted pairs with dual shield layers or single shield layer.
■ Fix and ground the cable protective cover using a piece of conductive metal.
■ The maximum cable length allowed between the drive and safety switch is 30 m.