EtherNet/IP Communication
‑251‑
Set Service Type to Get Attribute Single for reading parameters or Set Attribute
Single for writing to parameters. Class is fixed to 0x93, Attribute is fixed to 0x9, and
Instance is the decimal value converted from the parameter to be read. For example,
FD‑13, that is, FD0D, needs to be converted to the decimal value 64781, as shown in
the preceding figure.
Select a position for storing the parameter from the Destination Element drop‑down
list on the right. You can also click New Tag to create a variable.
Click the Communication tab to select the AC drive.
Click OK. The master will read the parameter and store the data to the selected
variable. You can choose LOGIC > Monitor Tags to view the value of the variable.
To write to a parameter, set the parameters according to the following figure.
Step 6: Set the DHCP function.
Note: IP addresses assigned by using the DHCP function are not retained upon power
failure.