Modbus Communication
‑38‑
2. Insert the terminal resistor jumper cap J3 on the expansion card to the right.
AC Drive Configuration
Set the following parameters on the AC drive: Set F0‑02 to 2 (set the command source
to communication), and set F0‑03 to 9 (set the main frequency reference source to
communication).
Set the ones place of FD‑00 to 5.
Set FD‑01 to 0.
Set FD‑03 to 2.
Set FD‑04 to 0.0.
Record the address of FD‑02. It is the station number of the AC drive.
PLC Configuration
1. Connect the PC and PLC by using a network cable or USB, open InoProShop, and
create a new project.
2. Click Standard Project, change the project name and location, and click ""OOKK"".