Option Selection
‑145‑
290±0.5
356±2
536±3
64±0.5
082 ±3
169±2
10
2- 13
50
26
20
17
90
25
25
230±2
220±3
93.5±2
255±1
64±0.5
6- 13
2-M12
Figure 4‑27 Dimensions of JIANLI filters (1000 A) (unit: mm)
4.3.4 Simple Filter
A simple filter can be used to suppress the RF electromagnetic noise from the power
grid and the AC drive during operation. For an AC drive with an earth leakage circuit
breaker, a simple filter can be installed on the input side to prevent malfunction of
the earth leakage circuit breaker.
The simple filter must be grounded securely and the cable between the filter and AC
drive must be shorter than 30 cm. The grounding terminal of the simple filter must be
connected to the grounding terminal of the drive, and the grounding cable must be as
short as possible and cannot exceed 30 cm.