Electrical Design
‑91‑
Figure 3‑34 Multi‑device system connection with a repeater
Baud rates and communication distances
Baud Rate
(kbps)
9.6 19.2 93.75 187.5 500 1500 3000 12000
Transmis
sion
Distance
(m)
1200 1200 1200 1200 400 200 100 100
Note
The transmission distances in the preceding table are distances without using any repeater.
3.5.4 PROFINET IO Industrial Ethernet Communication
3.5.4.1 Overview
The PROFINET I/O Industrial Ethernet adapter module (MD580‑SI‑PN1 for short)
meets international PROFINET I/O Industrial Ethernet standards. The module is used