‑15‑
Note
For three‑phase 380 V to 480 V AC drives, reactors are not available for T1 to T4
models, whereas DC reactors are standard for T5 models and above.
For three‑phase 380 V to 480 V AC drives, braking units are standard for T1 to T4
models and optional for T5 to T8 models.
The output current refers to the rated output current for light overload (P‑type AC
drive).
Mark "L" indicates that the AC drive has a base for installing an AC output reactor.
1.3 Technical Data
1.3.1 Electrical Specifications
The rated power of AC drives in the following tables is measured on three‑phase 380 V
to 480 V models at the input voltage of 400 VAC.
AC drive application modes are classified into the light load mode (P‑type AC drives)
and heavy load mode (G‑type AC drives).
The light load mode is represented by the uppercase letter "P". P‑type AC drives
comply with requirements of rated power, rated input current, rated output
current, and overload curve in this mode.
The heavy load mode is represented by the uppercase letter "G". G‑type AC drives
comply with requirements of rated power, rated input current, rated output
current, and overload curve in this mode.
To facilitate distinction, P‑type AC drive parameters are suffixed with "P" and G‑
type AC drive parameters are suffixed with "G". Data in this guide is from P‑type AC
drives unless otherwise specified.